For several years, CHANGXIN have specialized in trading high-quality components in the field of industrial automation.
Focusing on PLC components, DCS and CNC technology, and drivetechnology
Shinkawa VM-721B/TB1 18 channel programmable relay output module
| Brand: Shinkawa VM-7 series TSI system |
| Item NO: VM-721B/TB1 |
| Effect: Collect warning, danger, and fault signals from various monitoring modules within this rack |
| Condition: In stock, brand new/Used |
| Warranty: 365 days |
| Payment:T/T 50% deposit, 50% balance |
| www.szcxdcs.com |
+86 15359298293
Shinkawa VM-721B/TB1 18 channel programmable relay output module
VM-721B/TB1 is an 18 channel programmable relay output module for the Shinkawa VM-7 series TSI system in Japan./TB1 represents the supporting front plug-in terminal version and can only be installed in the designated slot of the VM-761B rack. The alarm status of all monitoring modules in the rack is read through the rack backplane bus.
Function: VM-721B/TB1 collects warning, danger, and fault signals from various monitoring modules such as vibration, displacement, speed, and temperature within this rack; Internally perform programmable logic operations (AND, OR, non logical combinations) and output 18 independent relay dry contacts; Output unit comprehensive alarm and trip interlock contacts to DCS and interlocking system; VM-721B/TB1 is used to expand the number of system alarm output contacts, achieve logical combination of multiple measurement point alarms, complete the output of hard contacts for rotating machinery protection interlocking, and compensate for the problem of insufficient relay channels in a single monitoring module.
————————Shenzhen Changxin Automation Equipment Co Ltd -————————
Products that have been released are welcome for consultation. Due to the wide variety of models, we were unable to upload physical images one by one!

Parameter Specifications
| Parameter | Value |
|---|---|
| Model | VM‑721B/TB1 |
| Product family | VM‑7 Series TSI System |
| Module type | 18‑channel programmable relay module |
| Termination option | /TB1 front‑plug terminal block |
| Install slot | Only for slot11 of VM‑761B chassis |
| Total relay output | 18 channels relay dry contact |
| Contact rating | 250 V AC / 30 V DC, 2 A per contact |
| Logic function | AND / OR / NOT combinatorial logic |
| Logic elements | Max 255 elements per relay channel |
| Backplane bus | VM‑7 rack internal backplane bus |
| Power supply | Supplied by rack backplane 24 V DC |
| Power consumption | <12 W |
| Hot‑swap | Hot‑swappable |
| Operating temperature range | 0 ~ +60 ℃ |
| Storage temperature range | ‑20 ~ +70 ℃ |
| Relative humidity | 5‑95% non‑condensing |
| Dimension(W×H×D) | 45 ×120 ×210 mm |
| Weight | 0.65 kg |
| Origin | Japan |
Product features
- There are a total of 18 relay dry contact outputs that support software configuration logic operations. The Alert warning, Danger danger, and module fault signals from any measuring point in the rack can be combined and/or non logically to generate comprehensive alarm and trip signals, greatly expanding the TSI system’s hard contact output capability.
- TB1 configuration front plug-in Phoenix terminal block, wiring maintenance does not require dismantling the cables on the back of the rack, making it easy to repair and replace modules
- Supports hot swapping, and modules can be replaced without powering on the rack, without affecting the normal protection function of other vibration monitoring modules inside the rack.
- It can only be fixedly installed in slot 11 of VM-761B rack, and the alarm status of the entire rack can be obtained through the backplane bus. It cannot operate independently.
- Cooperate with MCL View software to complete logical configuration, and each relay can be freely bound to different measurement point alarm conditions to meet the complex interlocking logic requirements of the unit.
- The panel LED indicator light intuitively displays the relay output status and backplane bus communication faults.

Product Recommendation:
Shinkawa VM-742B1-5 upper network communication module
Shinkawa VM-701B VM-7 Series Vibration/Displacement Monitoring Module
GE Mark VIe Series IS220PCNOH1B CANopen Communication I/O Module
T8461C | ICS TRIPLEX Trusted TMR Digital Output Module
GDB021BE01 HIEE300766R0001 Multi-channel Current Acquisition Module
ABB 3BHB030310R0001 5SHY4045L0006 3BHE039203R0101 GVC736CE10 IGCT series power module
PM866A 3BSE076359R1 ABB 800xA System Core Processor Unit (CPU)
PM511V16 3BSE011181R1 ABB Digital signal processing control board

Usage Scenarios
- 1. The TSI system for steam turbines in thermal and gas-fired power plants expands a large number of comprehensive alarm and unit trip hard contact outputs, which are sent to ETS and DCS interlocking systems.
- Petrochemical turbine centrifugal compressor unit, multi measuring point alarm logic combination, output interlocking shutdown contact.
- When the number of relay channels in the original monitoring modules of large-scale rotating equipment in coal chemical and refinery plants is insufficient, this module is added to expand the dry contact output.
- Replacement of stock Shinkawa VM-761B rack system spare parts, direct replacement of damaged VM-721B/TB1 in situ, using the original logic configuration and wiring terminals.
- Factory renovation project, without replacing the entire TSI hardware, adding combined alarm output to achieve complex unit protection logic.