Product Categories
CHANGXIN Module Spare Parts

For several years, CHANGXIN have specialized in trading high-quality components in the field of industrial automation.

Focusing on PLC components, DCS and CNC technology, and drivetechnology

Get Instant Quote
Contact Form Demo (#3)

Shinkawa VM-721B/TB1 18 channel programmable relay output module

Brand: Shinkawa VM-7 series TSI system
Item NO: VM-721B/TB1
Effect: Collect warning, danger, and fault signals from various monitoring modules within this rack
Condition: In stock, brand new/Used
Warranty: 365 days
Payment:T/T 50% deposit, 50% balance
www.szcxdcs.com
Telephone

+86 15359298293

Product Description

Shinkawa VM-721B/TB1 18 channel programmable relay output module

VM-721B/TB1 is an 18 channel programmable relay output module for the Shinkawa VM-7 series TSI system in Japan./TB1 represents the supporting front plug-in terminal version and can only be installed in the designated slot of the VM-761B rack. The alarm status of all monitoring modules in the rack is read through the rack backplane bus.

Function: VM-721B/TB1 collects warning, danger, and fault signals from various monitoring modules such as vibration, displacement, speed, and temperature within this rack; Internally perform programmable logic operations (AND, OR, non logical combinations) and output 18 independent relay dry contacts; Output unit comprehensive alarm and trip interlock contacts to DCS and interlocking system; VM-721B/TB1 is used to expand the number of system alarm output contacts, achieve logical combination of multiple measurement point alarms, complete the output of hard contacts for rotating machinery protection interlocking, and compensate for the problem of insufficient relay channels in a single monitoring module.

————————Shenzhen Changxin Automation Equipment Co Ltd -————————

Products that have been released are welcome for consultation. Due to the wide variety of models, we were unable to upload physical images one by one!

SHINKAWA VM 7 1

Parameter Specifications
Parameter Value
Model VM‑721B/TB1
Product family VM‑7 Series TSI System
Module type 18‑channel programmable relay module
Termination option /TB1 front‑plug terminal block
Install slot Only for slot11 of VM‑761B chassis
Total relay output 18 channels relay dry contact
Contact rating 250 V AC / 30 V DC, 2 A per contact
Logic function AND / OR / NOT combinatorial logic
Logic elements Max 255 elements per relay channel
Backplane bus VM‑7 rack internal backplane bus
Power supply Supplied by rack backplane 24 V DC
Power consumption <12 W
Hot‑swap Hot‑swappable
Operating temperature range 0 ~ +60 ℃
Storage temperature range ‑20 ~ +70 ℃
Relative humidity 5‑95% non‑condensing
Dimension(W×H×D) 45 ×120 ×210 mm
Weight 0.65 kg
Origin Japan
Product features
  1. There are a total of 18 relay dry contact outputs that support software configuration logic operations. The Alert warning, Danger danger, and module fault signals from any measuring point in the rack can be combined and/or non logically to generate comprehensive alarm and trip signals, greatly expanding the TSI system’s hard contact output capability.
  2. TB1 configuration front plug-in Phoenix terminal block, wiring maintenance does not require dismantling the cables on the back of the rack, making it easy to repair and replace modules
  3.  Supports hot swapping, and modules can be replaced without powering on the rack, without affecting the normal protection function of other vibration monitoring modules inside the rack.
  4. It can only be fixedly installed in slot 11 of VM-761B rack, and the alarm status of the entire rack can be obtained through the backplane bus. It cannot operate independently.
  5. Cooperate with MCL View software to complete logical configuration, and each relay can be freely bound to different measurement point alarm conditions to meet the complex interlocking logic requirements of the unit.
  6. The panel LED indicator light intuitively displays the relay output status and backplane bus communication faults.

SHINKAWA VM 5H3 VM 5P3 VM 5Z4 1 副本 SHINKAWA VM 5Y1 02GEM 1594 005 P001G 2 副本

Product Recommendation:

Shinkawa VM-742B1-5 upper network communication module

Shinkawa VM-701B VM-7 Series Vibration/Displacement Monitoring Module

GE Mark VIe Series IS220PCNOH1B CANopen Communication I/O Module

T8461C | ICS TRIPLEX Trusted TMR Digital Output Module

GDB021BE01 HIEE300766R0001 Multi-channel Current Acquisition Module

ABB 3BHB030310R0001 5SHY4045L0006 3BHE039203R0101 GVC736CE10 IGCT series power module

PM866A 3BSE076359R1 ABB 800xA System Core Processor Unit (CPU)

PM511V16 3BSE011181R1 ABB Digital signal processing control board

ABB PM866A 3BSE076359R1 1

Usage Scenarios
  • 1. The TSI system for steam turbines in thermal and gas-fired power plants expands a large number of comprehensive alarm and unit trip hard contact outputs, which are sent to ETS and DCS interlocking systems.
  • Petrochemical turbine centrifugal compressor unit, multi measuring point alarm logic combination, output interlocking shutdown contact.
  • When the number of relay channels in the original monitoring modules of large-scale rotating equipment in coal chemical and refinery plants is insufficient, this module is added to expand the dry contact output.
  • Replacement of stock Shinkawa VM-761B rack system spare parts, direct replacement of damaged VM-721B/TB1 in situ, using the original logic configuration and wiring terminals.
  • Factory renovation project, without replacing the entire TSI hardware, adding combined alarm output to achieve complex unit protection logic.