Honeywell LG1093AA24 UV Flame Probe – Combustion Management System

Brand: Honeywell
Item NO: LG1093AA24
Effect: Flame UV signal acquisition
Condition: In stock, brand new/Used
Warranty: 365 days
Payment:T/T 50% deposit, 50% balance
www.szcxdcs.com
Telephone

+86 15359298293

Product Description

Honeywell LG1093AA24 UV Flame Probe – Combustion Management System

LG1093AA24 is a Honeywell LG1093 series ultraviolet UV flame probe designed specifically for gas turbines and industrial burners. It is used in conjunction with flame amplifiers/combustion management systems (BMS) to determine flame status by collecting ultraviolet radiation signals from flames. It is widely used in GE gas turbines, power station boilers, and petrochemical heating furnaces. LG1093AA24 is a front-end sensing component for combustion safety protection, with a PTFE shielded cable and a stainless steel probe housing that can be directly installed at the observation port of high-temperature and high-pressure combustion chambers. It is a key component of the unit’s flameout protection circuit.

火焰探测器 副本

————————Shenzhen Changxin Automation Equipment Co Ltd -————————

Products that have been released are welcome for consultation. Due to the wide variety of models, we were unable to upload physical images one by one!

长欣外网名片 2

HONEYWELL CC IP0101

Product function
  1. Flame UV signal acquisition: Sensing the ultraviolet radiation emitted by the burning flame, converting the light signal into a weak electrical signal, and transmitting it to the rear flame amplification module.
  2. Flame detection: Real time monitoring of the ignition, normal combustion, and extinguishing status of the burner. The probe itself does not make logical judgments, and the signal is sent to the BMS system for processing.
  3. Source of ignition safety protection trigger: Once the flame is extinguished and there is no ultraviolet signal output from the probe, the BMS will receive the signal loss and trigger fuel cut-off and unit interlock shutdown to prevent the risk of gas leakage and explosion.
  4. Suitable for various fuel conditions of gas turbines and boilers, supporting flame detection of various fuels such as natural gas and fuel oil.
  5. On site collection under harsh working conditions: directly facing the high-temperature and high-pressure environment of the furnace, complete on-site optical signal pickup, and transmit the signal to the processing unit inside the control cabinet through long-distance shielded cables.

Honeywell LG1093AA24 UV Flame Probe – Combustion Management System

Item Specification
Part Number LG1093AA24
Brand Honeywell
Alternative GE PN 261A1812P012
Detection Principle Ultraviolet (UV) flame sensing
Mount Thread 3/4‑inch NPTF internal
Conduit Thread 1‑inch external thread
Window Pressure Rating 150 psig @ 400°F
Operating Temperature(Sensor Head) ‑40 °C ~ +177 °C
Cable Material Teflon shielded cable
Available Cable Length 16ft(4.9m),42ft(12.8m),61ft(18.6m)
Response Time 0.1s typical
Certification ATEX, CE, FM
Application Gas turbine, industrial burner, boiler BMS system
Weight Approx.3.0 kg
Origin USA

CCC TMPU 1002 2 HONEYWELL TC CCN014 3

GE Mark VIe Series IS220PCNOH1B CANopen Communication I/O Module

T8461C | ICS TRIPLEX Trusted TMR Digital Output Module

GDB021BE01 HIEE300766R0001 Multi-channel Current Acquisition Module

ABB 3BHB030310R0001 5SHY4045L0006 3BHE039203R0101 GVC736CE10 IGCT series power module

PM866A 3BSE076359R1 ABB 800xA System Core Processor Unit (CPU)

PM511V16 3BSE011181R1 ABB Digital signal processing control board

PM891 | 3BSE053240R1 | ABB Central Processing Unit (CPU) Module

3BHE014070R0101 | PPC905AE101 | ABB PLC logic controller board

ABB CI860K01 3BSE032444R1 CI860K01 Implement fieldbus interface function

Product features
  1. The principle of ultraviolet detection only responds to the flame ultraviolet band, effectively avoiding the interference of high-temperature infrared thermal radiation in the furnace and reducing the probability of false alarms.
  2. The stainless steel probe body is resistant to high furnace pressure, and the observation window can withstand high temperature and pressure, suitable for harsh working conditions of gas turbines and boilers
  3. Factory integrated PTFE high-temperature shielded cable, resistant to electromagnetic interference, supports long-distance wiring between probes and control cabinets.
  4. Fast response speed, able to quickly capture flame establishment and extinguishing, ensuring timely response of the protection circuit.
  5. Explosion proof certification can be used in hazardous explosion areas of petrochemical and power plants.
  6. 3/4 “NPT internal thread standard installation interface, convenient for installation and fixation in the observation window of combustion equipment.
  7. The probe only outputs weak photoelectric signals and cannot work independently. It must be equipped with a backend flame amplifier/BMS system, and cannot achieve flame judgment and interlock output independently.